Electrical installation
4.8 Signal connections
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
67
S5: Selector for voltage/current AI0, AI1
Table 4- 11 Selector for voltage/current S5
Switch Function
S5.0 Selector voltage (V) / current (I) Al0
S5.1 Selector voltage (V) / current (I) Al1
Note
When delivered, both switches are set to current measurement (switch set to "I").
X522: 2 analog outputs, temperature sensor connection
Table 4- 12 Terminal block X522
Terminal Designation
1)
Technical specifications
1 AO 0V+
2 AO 0-
3 AO 0C+
4 AO 1V+
5 AO 1-
6 AO 1C+
-10 V - +10 V (max. 3 mA)
+4 mA - +20 mA (max. load resistance ≤ 500 Ω)
-20 mA - +20 mA (max. load resistance ≤ 500 Ω)
0 mA - +20 mA (max. load resistance ≤ 500 Ω)
Resolution: 11 bits + sign
continued short-circuit proof
7 +Temp
8 -Temp
Temperature sensor connection: KTY84-1C130 / PTC
1)
AO xV: analog output voltage; AO xC: Analog output current
Max. connectable cross-section: 1.5 mm²
CAUTION
The permissible back EMF at the outputs is ±15 V