Mechanical installation
3.3 Installation
Drive converter cabinet units
36 Operating Instructions, 10/2008, A5E00288214A
3.3.2 Preparation
On-site requirements
The cabinet units are designed for installation in closed, electrical operating areas in
compliance with EN 61800-5-1. A closed electrical operating area is a room or area
containing electrical equipment which can be accessed by trained personnel only. Access is
controlled by a door or other form of barricade which can be opened only by means of a key
or other tool. The room or area is also clearly signed with appropriate warning notices.
The operating areas must be dry and free of dust. The air supplied must not contain any
electrically conductive gas, vapors, or dust, which could impair operation. It may be
necessary to filter the air supplied to the installation room. If the air contains dust, filter mats
(option M54) can be installed in front of the ventilation grilles in the cabinet doors and also in
front of the hoods, if necessary. Option M54 offers additional protection against water
sprayed against the housing from any direction and corresponds to degree of protection
IP54.
The permissible values for climatic ambient conditions must be taken into account.
At temperatures > 40°C (104°F) and altitudes > 2000 m, the devices must be derated.
The basic version of the cabinet units complies with the IP20 degree of protection in
accordance with EN 60529.
The built-in units are installed in accordance with the dimension drawings supplied. The
clearance between the top of the cabinet unit and the ceiling is also specified on the
dimension drawings.
The cooling air for the power unit is drawn in from the front through the ventilation grilles in
the lower part of the cabinet doors. The warmed air is expelled through the perforated top
cover or the ventilation grilles in the top cover (with option M13/M23/M43/M54/M78). Cooling
air can also be supplied from below through raised floors or air ducts, for example. To allow
this, you have to create openings in the 3-section bottom plate.
According to EN 61800-3, the cabinet units are not suitable for use in low-voltage public
networks that supply residential buildings. High-frequency interference may occur if it is used
in this type of network.
Additional measures (e.g. line filter, option L00) can be fitted for use in the first environment
to EN 61800--3 category C2.
Unpacking the cabinets
Check the delivery against the delivery note to ensure that all the items have been delivered.
Check that the cabinet is intact.
The packaging material must be discarded in accordance with the applicable country-specific
guidelines and rules.