Electrical installation
4.8 Signal connections
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
65
Note
The digital inputs (terminals -X520 and -X530) in the example are powered by the internal
24 V supply of the customer terminal block (terminal -X540).
The two groups of digital inputs (optocoupler inputs) have a common reference potential for
each group (ground reference M1 or M2). To close the circuit when the internal 24 V supply
is used, the ground references M1 / M2 must be connected to internal ground (M).
If power is not supplied from the internal 24 V supply (terminal -X540), the jumper between
ground M1 and M or M2 and M must be removed in order to avoid potential rounding. The
external ground must then be connected to terminals M1 and M2.
X520: 4 digital inputs
Table 4- 8 Terminal block X520
Terminal Designation
1)
Technical specifications
1 DI 0
2 DI 1
3 DI 2
4 DI 3
Voltage: - 3 V to 30 V
Typical current consumption: 10 mA at 24 V
Reference potential is always terminal M1
Level:
- high level: 15 V to 30 V
- low level: -3 V to 5 V
5 M1 Ground reference
6 M Electronics ground
1)
DI: digital input; M1: ground reference; M: Electronics ground
Max. connectable cross-section: 1.5 mm²
Note
An open input is interpreted as "low".